After installation is completed, the Security System should be carefully
tested.
1. With the System in the disarmed state, check that all zones are intact.
If NOT READY is displayed, press READY key to display the faulted
zone(s). Restore faulted zone (s) if necessary, so that READY is
displayed.
2. Enter the security code and press the TEST key The external
sounder (if used) should sound for 3 seconds and then turn off (the
system is operating on the back-up battery only at this time).
Note 1. The system will not enter the TEST mode, (f the battery vol-
tage is too low, if Ihe battery is not connected, or if any com-
munication messages are pending their transmission.
Note 2. As a reminder that the system is in the TEST mode, the Con-
trol will sound a single beep at 15-second intervals if no pro-
tection zones are violated.
Note 3. In the TEST mode, no reports will be sent to the central sta-
tion.
Note 4. In TEST mode, the external sounder (if used) will not activate
3. Doors and windows: Open and close each protected door and
window in turn. Each action should produce three beeps from the
Control. The identification numbers for each protection zone WIII
aPPear on the Control display,
4. Motion detector= Walk in front of any interior motion detectors (if
used). Lislen for three beeps when the detector senses movement
While it is activated, its identification number will remain displayed on
the Control.
5, Smoke detectors: Follow the test procedure provided by the manufac-
turer of each smoke detector to ensure that all detectors are opera-
tional and are functioning properly. Note: A Zone 1 2-wire smoke
detector display will not clear until the Test mode is exited.
6. To turn off the TEST mode, enter the security code and press the
OFF key.
A message WIII be sent to the central station during the following tests.
No(lfy the central station that a lest will be in progress
NOTE: A display of “FC mdlcates a failure to communicate (no Kissoff
by the receiver at the central sta~ion after the maximum number
of transmleslon attempts is tried).
7 Arm the system and fault one or more zones.”Silence alarm sounder(s)
each time by entering the code and pressing OFF. Check Entry/Exit
delay zones
8 Check the keypad-initiated alarms by simultaneously pressing the
Panic keys (* and #, land *, and/or 3 and #). If the system has been
programmed for audible emergency, the Control will emit a loud,
steady alarm sound, and ALARM and “99” will be displayed for * and
# (if 1 and * are pressed, “95” wdl be displayed; If 3 and # are
pressed, “96” will be dmplayed). Silence the alarm by entering the
security code and pressing OFF.
If the system has been programmed for silent emergency, there will be
no audible alarms or displays, but a report will be sent to the central
station.
Notify the central station that all tests are finished, and verify results with
them.