VISTA-128BP/VISTA-250BP Installation and Setup Guide
4-4
MAIN MENU
OPTIONS
SCHEDULED CHK-IN
1 = YES 0 = NO 0
For defining the schedule for the system to automatically call the downloader.
Following is a list of commands used while in the Menu Mode:
#93 Menu Mode Programming Commands
#93
Enters Menu Mode.
[
✳
]
Serves as [ENTER] key. Press to have keypad accept entry.
[#]
Backs up to previous screen.
0
Press to answer NO.
1
Press to answer YES.
00, or 000+[
✳
]
Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.
Zone Number Designations
The VISTA-128BP supports up to 128 zones, the
VISTA-250BP supports up to 250 zones, of hardwire,
polling loop and/or wireless protection, distributed
among up to 8 partitions. The following table lists the
zone numbers and the types of sensors that can be used
with each, and some alternate functions of the zones.
Zone
Function
1
2-wire Smoke Detectors (if used)
5
Audio Alarm Verification (if used)
7
Keyswitch (if used)
8
Latching-Type Glassbreak Detectors (if used)
1-9
Traditional Hardwired Zones
9
RS232 Input (if used)
1-250
5800 Series Wireless Devices
10-250
Polling Loop Devices
995
✳
+ 1 Panic
996
# + 3 Panic
999
✳
+ # Panic
Zone Defaults
Zone #
Zone Type
Zone #
Zone Type
001
09
601-632
00
002
03
800-830
00
003
03
970
00
004
03
988
00
005
03
990
00
006
03
992
N/A
007
03
995
00
008
03
996
00
009
03
997
05
010–250
00
999
06
NOTE:
Zone 992 is the Duress zone. Programming of the
zone response type is not applicable. This zone requires only
the report code programming.
Zone Index
The zones are designated as follows:
ZONE #
RANGE
ZONE
FUNCTION
ACTUAL ZONE
001 – 250
Protection
zones
As indicated
601 – 632
Relay
Supervisory
Zones
6 + 2-digit Relay Number; e.g.,
Relay Number 03, if supervised,
is zone 603.
800 – 830
ECP Device
Supervisory
Zones
8 + 2-digit Device Address;
e.g., Device Address 01, if
supervised, is zone 801.
4285/4286 VIP Module is zone
804 (because its Device
Address must be set to 4).
TeleSmart is zone 824
(because its Device Address
must be set to 24).
970, 988,
990, & 997
System
Supervisory
Zones
970: Bell Supervision
988: 2
nd
Wireless Receiver –
not receiving signals
990: 1
st
Wireless Receiver –
not receiving signals
997: Polling Loop (short
circuit)
992, 995 –
999
Duress and
Keypad Panics
992: Duress
995: 1 +
✳
panic (A key)
996: 3 + # panic (C key)
999:
✳
+ # panic (B key)
Supervisory zones should be given a response type of 05
(Trouble by Day, Alarm by Night).