VISTA-128BP/VISTA-250BP Installation and Setup Guide
5-12
FIELD
TITLE and DATA ENTRIES EXPLANATION
1*74
Relay Timeout XXX Minutes
Enter
000-127
times 2 minutes (000-254).
This is used for #80 Menu Mode Time-Driven event relay command
numbers 04/09 and
Output Programming
in the
#93 Menu Mode
Programming
output command 56.
1*75
Relay Timeout YYY Seconds
Enter
000-127
seconds.
This is used for #80 Menu Mode Time-Driven event relay command
numbers 05/10 and
Output Programming
in the
#93 Menu Mode
Programming
command 57.
1*76
Access Control Relay (partition-
specific)
01-96
= relay number
00
= relay not used.
If enabled, the assigned relay closes for 2 seconds when the user enters
his code and presses 0.
Must be
00
for UL installations.
NOTE:
See
SECTION 3: Installing the Control
for enhanced access
control capabilities.
2*00
Number of Partitions
Enter
1-8
.
Enter the number of partitions used in the system.
2*01
Daylight Saving Time Start/End
Month
0
= disable
1
= enable
Enter the months (
00-12)
in which daylight saving time starts and ends.
Enter
00, 00
if daylight saving time does not apply to the users region.
Standard setting for U.S. is 04,10.
2*02
Daylight Saving Time Start/End
Weekend
0
= disable
1
= enable
Enter the start and end weekends for daylight saving time as follows:
1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from
last. Standard setting for U.S. is 1,5.
U
L
Fields 2*05 2*08 must be set to 0 for UL installations.
2*05
Auto-Arm Delay (partition-
specific)
00
= no delay.
01-14
times 4 minutes (04-56) delay.
15
= no auto arming.
This is the time between the end of the arming window and the start of
auto-arm warning time (field 2*06).
2*06
Auto-Arm Warning Period
(partition-specific)
01-15
times 1-minute warning.
00
= no warning period.
This is the time that the user is warned by a keypad sounding and display
to exit the premises prior to auto arming of the system.
2*07
Auto-Disarm Delay (partition-
specific)
00
= no delay.
01-14
times 4 minutes (04-56) delay.
15
= no auto disarming.
This is the time between the end of the disarming window and the start of
auto disarming of the system.
2*08
Force Arm Enable for Auto-Arm
(partition-specific)
0
= disable
1
= enable
If enabled, the system automatically bypasses any faulted zones when it
attempts to auto-arm.
If disabled, the system will not auto-arm.