FIELD TITLE and DATA ENTRIES EXPLANATION
*92
Phone Line Monitor Enable
Entry 1Timeout:
0 = disabled
1-15 = 1 minute to 15 minutes respectively
(2 = 2 min, 3 = 3 min, etc.; # + 10 =10 min, #
+ 11 = 11 min, # + 12 = 12 min, # + 13 = 13
min, # + 14 = 14 min, # + 15 = 15 min)
Entry 2Display/Sound:
0 = keypad display only when phone line is
faulted.
1 = keypad display plus keypad trouble
sound when line is faulted. Each
partition turns off its own trouble sound.
No automatic timeout.
2 = Same as “1” plus programmed output
device STARTS. If either partition is
armed, external sounder activates.
External sounder will be turned off by
normal bell timeout, or by security code
plus OFF from either partition (it does
not have to be the one that was armed).
Entry 1:
Sets the length of time a phone line fault must remain after
detected before the second digit option is activated.
Entry 2:
Selects the desired phone line fault response.
Option 2 may be used even if a relay unit or Powerline carrier device
is not connected to the control.
Programmed Output Device must either be programmed to be
STOPPED in field 80 or STOPPED by entry of [security code] + [#]
+ 8 + device number. Partition in 80 should be set to 0, for STOP.
U
L
Field *92 must be enabled for fire alarm installations, UL
commercial burglar alarm installations and UL residential burglar alarm
installations.
If the control unit is used on a UL commercial burglar alarm system
which requires 2 methods of remote communication, then the control
units DACT and the other method of signal transmission must monitor
each other against communication failure and line fault. The fault must
be received and annunciated within 200 seconds of its occurrence.
*93
No. of Reports In Armed Period
per Zone (Swinger Suppression)
0 = unlimited number of reports
1 = 1 report per zone per armed period
2 = 2 reports per zone per armed period
This option can be used to limit the number of alarm/alarm restore
messages per zone sent to the central station in an armed period.
UL installations must be 0 (unlimited reports).
*94
Download Phone Number
Enter up to 20 digits as follows: 09, # +11
for
, # + 12 for “#”, # + 13 for a pause.
Enter the phone number of the downloading computer.
Do not fill unused spaces. End field by entering . To clear entries
from field, press 94.
*95
Ring Count For Downloading
0–15 = number of rings before control picks
up phone line .
NOTE:
If 15 is entered to bypass an
answering machine, and a 4285 or 4286
Phone Module is included in the system,
you should note the following:
When calling in from an off-premises
phone, the user should make the initial
call, allow 1 or 2 rings only, then hang
up, then call again. The phone module
will now seize the line, and 2 long tones
sound, followed by the usual voice prompt
for the access code. If this procedure is
not followed, phone module operation will
not be possible.
Refer to the chart below and program this field accordingly.
phone answer down-
module machine loading Set field
95 to
yes no no 1-14 (not 0)
yes yes no higher than number of rings set on
answer machine (e.g., if ans.
machine is 4 rings, set this field to
5). This allows access to the phone
module if the answer machine is off.
yes no yes 1-14 (not 0)
yes yes yes 15 (bypasses answer machine
)
no no no 0
no yes no 0
no no yes 1-14
no yes yes 15
*96
Command to Initialize CSID and
Subscriber Account Number
This is a command function, not a data field. Use this command, if
necessary, to reset all subscriber account numbers and the internal
CSID to the factory default values.
*97
Command to Reset System to
Factory Default Values
This is a command function, not a data field.
Pressing
97 resets
all data fields to the factory default values (shown on the
Program Form).
IMPORTANT:
Do not press
97 to load defaults if any
programming has been done previously data already
programmed into the system will be changed!
*98
Command to Exit Program Mode
(with installer code lockout)
Exits Programming Mode and prevents re-entry by:
Installer Code + [8] + [0] + [0]. To enter the programming
mode if
98 was used to exit, you must first power the system
down. Then power up again, and press [
] and [#] at the same
time, within 50 seconds of powering up.
See field *88 for other Program mode lockout options.
*99
Command to Exit Program Mode
Exits Programming Mode and allows re-entry by:
Installer Code + [ 8] + [0] + [0] or by: Pressing [
] and [#] at
the same time, within 50 seconds of power-up.
Installation Instructions