Pager Programming Fields
FIELD TITLE and DATA ENTRIES EXPLANATION
*160
Pager 1 Phone No.
Enter up to 20 digits
If you enter fewer than 20 digits, exit by pressing [] and next field
number. To clear entries from this field, press 160.
*161
Pager 1 Characters
Enter up to 16 characters
Up to 16 optional characters may be sent as a prefix to the 7-digit
system status code sent to pager #1 (if used). Phone number in field
*160 must have been entered. If fewer than 16 characters, exit by
pressing [] and next field number. To clear entries from this field,
press 161.
For example, these optional 16 characters may be composed of the
following:
PIN number (to identify a specific pager to the paging company)
Subscriber account number
(enter # + 11 to send )
# (enter # + 12 to send #)
Pause (enter # + 13 to allow a 2-second pause)*
Any special character(s) the end user may decide to transmit
* Some paging systems require pause(s) before the prefix.
The format for the 7-digit system status code is defined as follows:
Pager Format: XXX-YYYY where:
XXX = 3-digit event code: 911 = Alarm
811 = Trouble
101 = Opening (disarm)
102 = Closing (arm AWAY)
YYYY = 4-digit user or zone number (depending on type of event).
The first digit indicates partition (0 = system, 1 = part 1,
2 = part 2, 3 = common), followed by the 3-digit user or
zone number.
Example 1. Pager displays:
9111004
This indicates that the system is reporting an alarm (911) caused by
a fault in zone 4 (0004) in partition 1.
Example 2. Pager displays:
102 2005
This indicates that the system is reporting a closingsystem arming
(102) by User 5 (0005) in partition 2.
*162
Pager 1 Report Options
0 = No reports sent
1 = Open/close for all users enabled to page
4 = All alarms and troubles
5 = All alarms, troubles, and open/close for
all users enabled to page
12 = Alarms and troubles for zones entered
in zone list 9
13 = Alarms and troubles for zones listed in
zone list 9 and open/close for all users
enabled to page
Enter the types of reports to be sent to pager 1 for each partition.
Reports to pager only when arming (close)/disarming (open) from a
keypad using a security code; auto-arming/disarming, arming with
assigned button, and keyswitch arming do not send pager messages.
*163
Pager 2 Phone No.
Enter up to 20 digits
If you enter fewer than 20 digits, exit by pressing [] and next field
number. To clear entries from this field, press 163.
4-9
Zobrazit stránku 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 87 88