
Section 7 - 2-Wire Polling Loop Expansion
7-3
2. Wire each device to the polling loop, making sure to use correct polarity when making
connections (refer to the device's instructions). If you are using serial number
devices, and intend to have the control enroll each serial number
automatically, wire no more than 25 of these devices to the control at a time.
Then power up and program them before connecting the next 25. Leave previously
enrolled devices connected.
3. If you intend to manually enter the serial numbers through the keypad or through V-
LINK or Compass downloading software, all the devices may be connected before
powering up to program.
4. Note the polling loop devices that have DIP switches on them. Set each device's DIP
switches for the zone number you are assigning it. Refer to the device's instructions or
the DIP Switch Tables at the end of this manual when setting addresses.
Certain polling loop devices have a DIP switch which can be used either to select the device's
zone number or to select the enrolling of a unique, embedded serial number by the control panel.
When used with VISTA-128B, these devices
must
be set for the serial number mode of operation.
The 4297 Polling Loop Extender may be used to provide additional polling loop current, to
extend the polling loop wire run length, and/or to provide individual electrically isolated
polling loops. Refer to Figures 7-2 and 7-3, to follow.
DO NOT
use the 4197 Polling Loop Extender module with the VISTA-128B
.
Be sure to include the total current drawn on the polling loop when figuring the total auxiliary load
on the panel's power supply (use the AUXILIARY CURRENT DRAW WORKSHEET in the
Final
Power Up Procedure
section.
Komentáře k této Příručce