BASIC 9 HARD-WIRED ZONES
Zone 1 The following table summarizes zone 1 characteristics.
Applications Can be used for EOLR supervised or closed circuit
unsupervised devices. It is the only zone that supports
2-wire smoke detectors.
Zone Response Type: Any
Response Time 350 msec
Max. Zone Resistance 100 ohms, excluding EOLR
Unsupervised Usage Cut red PCB jumper.
Only closed circuit devices can be used.
EOLR Supervised Leave red PCB jumper intact.
Supports both open circuit and closed circuit devices.
Connect open circuit device in parallel across the loop.
The 2,000 ohm EOLR must be connected across the
loop wires at the last device.
Connect closed circuit device in series with the loop.
EOLR Fire Zone: Leave red PCB jumper intact.
Assign zone type 09 (fire)
Supports up to sixteen (16) 2-wire smoke detectors.
Second CODE + OFF sequence momentarily
interrupts power to reset the smoke detectors.
See table below for compatible detectors.
Compatible Smoke Detectors
Detector Type Device Model #
Photoelectric w/heat sensor, direct wire...................... System Sensor 2300T
Photoelectric plug-in head........................................ System Sensor 2600EC
Photoelectric, direct wire ......................................... System Sensor 2400
Photoelectric w/heat sensor, direct wire...................... System Sensor 2400TH
Photoelectric w/B401B base..................................... System Sensor 2451
Photoelectric w/heat sensor & B401B base ................. System Sensor 2451TH
Ionization, direct wire.............................................. System Sensor 1400
Ionization w/B401B base ......................................... System Sensor 1451
Ionization plug-in head ............................................ System Sensor 1600EC
Photoelectric duct detector
w/DH400 base ....................................................... System Sensor 2451
Ionization duct detect. w/DH400 base ........................ System Sensor 1451DH
Zone 1 Advisories
If the EOLR is not at the end of the loop, the zone is not properly supervised. The
system may not respond to an open circuit within the zone.
The alarm current provided by this zone is sufficient to support operation of only
one detector in the alarmed state.
UL NOTE: EOLR are required for UL installations.
Zone 9 The following table summarizes zone 9 characteristics.
Applications This zone is unsupervised and is suitable for monitoring
fast acting glass break sensors or vibration sensors when
programmed for fast response.
Response Type Any type except fire
Response Time Normal (350 msec) or Fast (10msec) selected in field *14.
Max. Zone Resistance 300 ohms
Unsupervised Usage Only closed circuit devices can be used.
• Connect these devices in series with one another
between terminals 22 & 23.
Zone 9 Advisories
Avoid using mechanical magnetic or relay type contacts in this zone when
programmed for fast response.